Cyberex® PowerBuilt™ Industrial UPS

Cyberex® PowerBuilt™ Industrial UPS

Single phase 10-80kVA

Categories: , ,

Cyberex PowerBuilt is a true online double-conversion ABB industrial UPS designed to support the continuing demand from downstream refining and petrochemical processing, upstream oil and gas processing, power generation, and the growing regulatory and safety needs of today’s industrial complexes.

Description

Cyberex PowerBuilt Industrial UPS Technical Specifications

 

General data
System power range 10, 15, 20, 30, 40, 50, 60, 80 kVA
UPS output rated PF  0.8
Max. no of parallel frames  Up to 2 frames
Topology  True online double conversion
Enclosure Dimensions  10 – 40 kVA*:  37″W x 34.25″D x 81.5″H
(*40 kVA high bus only)
40 – 80 kVA:    80″W x 38.25″D x 81.5″H
Input
Nominal input voltage 480 VAC 3W+G. Other voltages are also available
Input voltage range +10, -20%VAC from nominal
Input power factor 0.75 @ full load and nominal
Current walk-in Up to full load in > 10 seconds
Input current THD% 30–35% typical
DC bus/battery
DC voltage (nominal) 120VDC (60 cells nominal, up to 60 kVA)
240VDC (120 cells nominal)
DC range 105–140VDC/210–280VDC
DC regulation ± 1% over the full load
DC ripple ± 1% RMS of the DC battery voltage at 100%
load with the battery connected
DC-AC efficiency 86% (typical)
DC end volts 1.75 V/cell end volts
Output
Rated output voltage 120 VAC 2W+G  (other voltages are also available)
Voltage regulation <± 0.5% steady-state for 0 to 100%
load change
Transient response max. <± 15% for a 100% load step
Recovery Return to within ± 1% of nominal within
16 ms
Voltage distortion Linear loads: <± 2% @100% load
Non-linear loads: <± 4% @100% load
Overload Up to 150% for 10 minutes
Overload static bypass 1000% for 0.1 seconds
Frequency 60 Hz
Frequency stability ± 0.01%
Frequency slew rate Factory set 1Hz/s, user-adjustable range:
0.2 – 100Hz/s
Communications
User interface Full-colour touch screen monitor panel, 6″ X 8″
Communication ports USB Service Port, RS-485, Modbus RTU & ASCII
Indications Mimic, LED
Environmental
Acoustical noise level 65 dbA typical at 3 meters with redundant
fans
Operating temperature 0–40°C
Relative humidity 5–95% non-condensing
Enclosure Protection NEMA 1
Operating altitude Up to 1000 meters w/o derating load
Access No rear or side access required for operations
or maintenance
Online double conversion efficiency Typical 83% (kW out/kW in)
Cooling Air-cooled with redundant cabinet fans
Compliancy
Safety & Acceptance  NEMA/UL-1778
– CSA C22.2 no.107.3-0S
– IEC 62040-2, category 3
– IEC 62040-3 dynamic output classification 1 – sensitive critical loads
– ANSI/NFPA 70 (2014) – conductors

Technical specifications are subject to change without notice.