Modular UPS-HPM Family (25-1560kVA)

Modular UPS-HPM Family (25-1560kVA)

Adopting digital control design

Categories: , ,

HPM series UPS is developed as a high frequency on line modular UPS for medium and large data center, adopting fully digital control technology, fully guarantee power supply to operate reliably and stably; diversified option of modular power, accurately position user side requirements; flexible redundancy design greatly increase the system availabity, user can realize expansion as demand, and modular structure greatly increase the convenience for maintenance.

Description

General Features of Modular UPS-HPM Family

● Adopting digital control design, and the control system is more reliable

● High power density design, the capacity of the single power module is 6KVA/ 10KVA/ 15KVA/ 20KVA/ 25KVA/ 30KVA/ 40KVA, the height of all these modules is 3U. The power of the system ranged from 6KVA to 520KVA corresponds to the number of parallel power modules from 1 to 13

● The redundant control system, each power module is equipped independent control system, and control itself independently according to the sharing message, and the fault module separates from the system automatically

● Support parallel expansion for cabinet and parallel expansion is up to 4 cabinets.

● Voltage of batteries can be configured flexibly, 1 input 1 output/ 3 input 1 output ±96Vdc/ ±108Vdc/ ±120Vdc(16/18/20PCS)selectable; 3 input 3 output±216Vdc/±228Vdc/±240Vdc (32/34/ 36/38/40PCS) selectable

● Intelligent charging mode, Charging current can be configured, there is 3 charging mode which is constant current mode、constant voltage mode、floating charging mode, and the charging mode can be transferred smoothly.

Technical Specification of Modular UPS-HPM Family

MODEL HPM3325-250KVA HPM3330-90KVA HPM3330-150KVA HPM3330-300KVA HPM3340-200KVA HPM3340-320KVA HPM3340-400KVA HPM3340-520KVA HPM3340-800KVA HPM3340-1280KVA HPM3340-1560KVA
Capacity (VA/Watts) UPS cabinet 250k / 225k 90k / 81k 150k / 135k 300k / 270k 200k/180k 320k/288k 400k / 360k 520k / 468k 800k / 720k 1280k / 1152k 1560k / 1404k
HPM module   25k / 22.5k  25k / 22.5k, 30k / 27k 40k / 36k
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE)
Operating voltage range 208~478Vac for half load; 305~478Va c for full load
Operating frequency range 40~70Hz
Power factor ≥0.99
Harmonic distortion (THDi) 3%(100% non-linear load)
Bypass voltage range 380Vac Max.voltage: +25%(optional +10%,+15%,+20% )
400Vac Max.voltage: +20% (optional +10%,+15%)
415Vac Max.voltage: +15% (optional +10%)
Min.voltage: -45% (optional -20%,-30%)
Bypass frequency range Frequency synchronize tracing range:±10%
Generator access Support
OUTPUT
Rated voltage 380/400/415Vac(3Ph+N+PE)
Power factor 0.9
Voltage regulation ±1%
Frequency Line mode ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)
Bat. mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load
≤5% with non-linear load
Efficiency 95.00%
BATTERY
Battery voltage ±192/±204/±216/±228/±240Vdc; Battery quantity(optional)
Charging current(A) UPS cabinet 60A (Max.) 30A (Max.) 50A (Max.) 100A (Max.) 50A (Max.) 80A (Max.) 100A (Max.) 130A (Max.) 200A (Max.) 320A (Max.) 390A (Max.)
HPM module  6A (Max.)   25kVA:6A (Max.) / 30kVA:10A (Max.) 10A (Max.)
Backup time  Depends on the capacity of external batteries
SYSTEM FEATURES
Transfer time Utility to battery:0ms; Utility to bypass:0ms
Overload Line mode Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% turn to bypass mode immediately
Bat. mode Load≤110%: last 10min,≤125%: last 1min,≤150%: last 1S,≥150% shut down UPS immediately Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% shut down UPS immediately
Bypass mode  Breaker (25kVA:40A) Breaker ( 25kVA:40A / 30kVA:60A)  40kVA:95A
Short circuit Hold the whole system
Noise suppression Complies with EN62040-2
Communication interface UPS cabinet: RS232, RS485, Dry contact, Intelligent slot x 2(SNMP card, Relay card optional);
HPM series UPS module: RS232
ENVIRONMENT
Operating temperature 0~40℃
Storage temperature -25~55℃
Humidity range 0~95% (Non-condensing)
Altitude <1500m. When >1500m, derating power for use
Noise level <70dB <65dB <70dB <73dB
PHYSICAL
Dimension D×W×H (mm) UPS cabinet 1100×600×2000 840×600×1400 1100×600×2000 850×600×1600 850×600×2000 850×1200×2000 850×2000×2000 850×3400×2000 4800×850×2000
HPM module  443x580x131 (3U)
Net weight (kg) UPS cabinet 290 158 170 307 251 320 540 980 1400 2800
HPM module 32    25kVA/32; 30kVA/33.5 36
STANDARDS
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8