PCS100 UPS-I

PCS100 UPS-I

From 150 kVA to 3 MVA

Categories: , ,

Designed for commercial and industrial applications, ABB’s PCS100 industrial UPS has power ratings from 150 kVA to 3 MVA.

Description

PCS100 UPS-I Technical Specifications

Utility – Input
Rated Supply Voltage (according to model) 220 V (208 – 220 V)
400 V (380 – 400 V)
480 V (415 – 480 V)
Note: Operation at lower than the rated voltage results in less kVA per module. Consult the rating tables for more information
Voltage tolerance ± 10%
Nominal supply frequency 50 Hz or 60 Hz
Frequency tolerance ± 5 Hz
Maximum Continuous Voltage 110%
Power system 3 phase + Neutral (4-Wire) Centre ground referenced (TN-S)
Contact us for use in other power systems
Overvoltage category III
Fault capacity Refer to the model tables in the PCS100 UPS-I  technical catalogue
Efficiency (400 V & 480 V models) 99% (typical)
Efficiency (220 V models) 98% (typical)
Overload and Short Circuit Protection Circuit Breaker (not included)
Overload Capacity 120% for 60 s
150% for 30 s
200% for 10 s
300% for 5 sNot more than once every 10 minutes. For more information refer to the PCS100 UPS-I technical catalogue

 

Load – Output
Capacity Rating 150 kVA to 3000 kVA
Displacement Power Factor of Connected Load 0.5 lagging to 0.9 leading
Crest Factor for Rated kVA 2.0
Maximum allowed motor load 25% of rated kVA
Contact ABB for applications with greater than 25%
Overload Capability – Inverter 110% for 30 s

 

Inverter Supply
Maximum operating period 30 s at rated load
Transfer time ≤ 1.8 ms (typical)
Voltage Settling time ≤ 5 ms (typical)
Cooling Air-cooled, fan-forced
Minimum output voltage > 95% at the end of the discharge
Output Frequency 50 or 60 Hz
Inverter frequency equals the supply frequency.
Frequency accuracy 0.10%
Overload capability 110% for 30 s
Voltage distortion < 2.5% THDv for linear loads
Voltage unbalance
(negative / positive sequence)
<3% for 100% unbalanced loads
Fault capacity (short circuit) 120% of rated current

 

Fail-Safe Bypass
900 A Utility Disconnect Integrated normally closed contactors
2200 A & 4200 A Utility Disconnect Optional air circuit breaker (ACB)
Overload Capability 150% for 500 s
200% for 300 s
300% for 120 s
500% for 30 s
Note: Not more than once every 30 minutes.
Closing Time 900 A 20 ms
Closing Time 2200 & 4200 A 80 ms
Cooling Convection

 

Coupling Transformer
Capacity Rating 110% of PCS100 UPS-I kVA rating for 30 s
Note: Optimized for short-term performance.
Type Dry
UL Insulation Class N (200 °C)
Design Temperature Temperature rise 60 °C for a short-term full load operation
Typical Impedance 8%
Note: The PCS100 UPS-I incorporates impedance voltage compensation control methods

 

Energy Storage – Ultracapacitors
System DC Nominal Voltage 750 V DC
Discharging Voltage Range 750 V DC to 554 V DC
Overload Capacity 100%
Rated power 300 kW per string
Autonomy period 2 s @ 300 kW
For more information refer to the autonomy calculations in refer to the PCS100 UPS-I  technical catalogue
Operationg tempertaure  15 °C to 25 °C (recommended)
Design life  15 years at 25 °C
Cycle Life  > 500,000
Recharge time  < 45 s

 

Energy Storage – Batteries
System DC Nominal Voltage 672V DC (56 x 12V DC)
Discharging Voltage Range 780 V DC to 554 V DC
Overload Capacity 100%
Rated power 240 kW per string
Autonomy period 30 s @ 240 kW
For more information refer to ABB Document 2UCD120000E018
Operationg tempertaure 15 °C to 25 °C (recommended)
Design life 10 years at 25 °C
Cycle Life > 800 (full load 30 s discharge)
Recharge time < 30 min
System DC Nominal Voltage 672 V DC (56 x 12V DC)
Dsicharging Voltage Range 780 V DC to 554 V DC

 

Event Recording
Measurement Method Line to Line
Sample Time 125 µs
Resolution of timestamp in the event log 10 ms
Measurement Type Half-cycle RMS according to IEC 61000-4-30

 

Environmental
Operating temperature range 0° C to 40° C
32° F to 104° F
Operating altitude 1< 1000 m without derating
Capacity derating with altitude 1% every 100 m
above 1000 m
2000 m maximum
Humidity < 95%, non-condensing
Pollution degree rating  2
Noise  < 75dBA @ 2 m

 

Enclosure
Enclosure rating IP20 / NEMA 1
Material Electro-galvanized steel
Panel Thickness Side and Rear10 ms 1.5 mm
Panel Thickness Door 2 mm
Finish  Standard epoxy-polyester powder coating textured finish
Color  RAL7035
Enclosure Access  Hinged doors with key lock

 

User Interface
User Interface 10.1” colour touch panel
Touch panel Full parameter control
Control inputs

 

Start / Stop / Reset digital inputs
Control outputs Running, warning and fault relays

 

Serial Coms
Access protocol Ethernet connectivity
Modbus TCP

 

Standards and Certifications   
 Quality  ISO 9001
 Marking  CE
 Construction and safety  IEC 62040-1
 Electromagnetic Compatibility  IEC 62040-2, Category C3
 Performance  IEC 62040-3,
VFD SX 211 ≤ 450 kVA
VFD SS 211 > 450 kVA

Technical specifications are subject to change without notice.