SG Series IEC (Three-phase UPS)

SG Series IEC (Three-phase UPS)

From 10kVA to 500kVA

Three-phase UPS from 10kVA to 500kVA. Reliable and efficient standalone UPS for critical applications. The SG Series is one of the best performing, most reliable and most versatile three-phase UPS systems available to those who need critical power protection.

 

Description

SG Series IEC Three-phase UPS in BD:

This true online double conversion UPS exploits its network integration software and communication connectivity to provide comprehensive, easy-to-integrate power protection for almost any IT environment. The SG Series operates in VFI (voltage frequency-independent) mode, which maximizes load protection at any time. Instead of standard filters, the UPS runs an innovative control algorithm on the IGBT rectifier to ensure the delivery of clean power in a most efficient manner.

The SG Series IEC UPS provides top-class reliability and performance while complying with all relevant EMC and safety standards. ABB’s unique RPA™ technology (redundant parallel architecture) allows units to work in parallel, thus further increasing reliability and uptime. Orient.com.bd is the best website for you if you are looking for the best Online UPS Supplier in Bangladesh.

 Key features:

• eBoost technology for high efficiency – up to 99 per cent

• Up to 94.6 per cent efficiency

• PurePulse IGBT rectifier: clean input <2 percent THDi

• Output power factor: 1.0 (10-40 kVA), 0.9 (60-600 kVA)

• True front access design

• Small footprint

• Inverter zig-zag isolation transformer

• Extremely low output voltage distortion

• Superior battery management

• Intelligent energy management integrated (IEMi)

• Backfeed protection

• Built-in maintenance bypass

• Parallelable up to six units

SG Series IEC (Three-phase UPS) Technical specifications:

General data
System power range (KVA)
10-40; 60-80; 100-120; 160; 200-300; 400-500;
Active power / frame (kW)
10/15/20/30/40;  54/72;  90/108;  144;  180/225/270;  360/450
UPS output rated PF   0.9
Max no of parallel frames   Up to 6 frames
Max system power   Up to 30 modules
Max system power   3000 kW
Wiring   3ph + N + PE
UPS type   Three-phase standalone
Topology   Online double conversion
Input
Nominal input voltage 3 x 380/400/415 V + N
Voltage range 340-460 V
Frequency range 45-66 Hz
Current THD at 100% load < 3%
Power Factor at 100% load ≥ 0.99
Output
Rated output voltage (load dependent) 3 x 380/400/415 V + N
Voltage THD (with linear load) <2% linear load, <3% nonlinear load (EN 62040)
Rated frequency 50/60 Hz
Efficiency
Double conversion
Up to 92.3% Up to 91.9% Up to 92.1% Up to 94.2% Up to 94.6% Up to 94.2%
Eco-mode
Up to 98% Up to 97.9% Up to 97.9% Up to 98.4% Up to 98.5% Up to 98.7

 

Communications
User interface Multilingual graphic display (LCD)
Communication ports RS232, SNMP (Modbus IP, RS232, RS485 & BacNet IP)
Software Monitoring and shutdown software available as an option