TLE Series IEC (Three-phase UPS)

TLE Series IEC (Three-phase UPS)

From 160kW to 800kW

Three-phase UPS from 160kW to 800kW. Clean, reliable power for your critical load with ABB’s TLE Series UPS. TLE Series is one of the best-performing three-phase UPS systems for providing critical power protection in a wide range of applications. The UPS operates in VFI (voltage frequency independent) mode and uses an innovative control algorithm with three-level converter technology to achieve very high efficiency levels. This innovative product provides best-in-class efficiency in both double conversion mode and in eBoost™ operating mode.

Description

TLE Series IEC Three-phase UPS in Bangladesh:

TLE Series is one of the best-performing three-phase UPS systems for providing critical power protection in a wide range of applications. The UPS operates in VFI (voltage frequency-independent) mode and uses an innovative control algorithm with three-level converter technology to achieve very high-efficiency levels. This innovative product provides best-in-class efficiency in both double conversion mode and in eBoost™ operating mode.

The TLE Series IEC UPS provides industry-leading reliability and efficiency, as well as clean power and unity power factor at the output. Reliability can be further increased by using ABB’s unique RPA™ (redundant parallel architecture) technology to operate multiple units in parallel. Throughout their entire life cycle, all ABB UPS systems are fully supported by teams that provide training, application expertise and 24/7 preventive and corrective service. The popular branded UPS is available at Orient BD Limited showroom with the best features and UPS price in Bangladesh.

 Key features:

• eBoost, lithium batteries and RPA with intelligent energy management™ (IEM) further improve efficiency

• Input from mains conditioned to a sinusoid with 0.99 input power factor and <3 per cent THDi

• Double conversion efficiency up to 96.9 per cent

• Output power factor: 1

• True front access design

• Compact footprint

• Intuitive user interface

• Extremely low output voltage distortion

• Superior battery management

TLE Series IEC Technical Specifications

General data
System power range
160 kW 200 kW 320 kW 400 kW 600 kW 800 kW
Active power / frame
160 kW 200 kW 320 kW 400 kW 600 kW 800 kW
UPS output rated PF   1.0
Max no of parallel frames   Up to 6 frames
Max system power   4800 kW
Wiring   3ph + N + PE
UPS type   Three-phase standalone
Topology   Online double conversion
Input
Nominal input voltage 3 x 380/400/415 V + N
Voltage range 340-460 V
Frequency range 45-66 Hz
Current THD at 100% load < 3%
Power Factor at 100% load ≥ 0.99
Output
Rated output voltage (load dependent) 3 x 380/400/415 V + N
Voltage THD (with linear load) <2,5% linear load, <5% nonlinear load (EN 62040)
Rated frequency 50/60 Hz
Efficiency
Double conversion efficiency (VFI)
Up to 96.4% Up to 96.6% Up to 96.5% Up to 96.6% Up to 96.9% Up to 96.8%
In eco-mode configuration (eBoost*)
Up to 98.2% Up to 98.3% Up to 98.2% Up to 98.3% Up to 98.3% Up to 98.3%

 

Communications
User interface Multilingual graphic display (LCD)
Communication ports RS232, SNMP (Modbus IP, RS232, RS485 & BacNet IP)
Software Monitoring and shutdown software available as an option

* Optional feature for all available models