UBR (6-10kVA)

UBR (6-10kVA)

True double-conversion

UB series UPS can supply reliable power to data center crucial load, meet the high reliability of customer for UPS. Deployment is very flexible, tower deployment and rack-mounted can be configured according to customer’s requirement. UB is with high efficiency and can supply comprehensive power protection for the user.

You can buy from best after sales service provider for UPS in Bangladesh.

Description

General Features

● True double-conversion

● The rack-mounted and floor-standing tower can be convertible

● Patented Minic LCD of which content can be rotated according to the type of deployment

● DSP technology guarantees high reliability

● N+X parallel redundancy

● Selectable quantity of battery for each group:16/18/20 pieces

● Adjustable charging current via LCD

● 3-stage charging design optimizes battery performance

● ECO mode operation for energy saving

● Self-diagnosis at startup

● Emergency power off function(EPO)

● Maintenance bypass is convenient for maintenance

● Generator compatible

● PDU is convenient for connecting load

● Communications:RS-232,USB,SNMP card(Optional), Relay card (Optional)

● Cold start

Technical Specification

MODEL UBR60L UBR100L
Capacity (VA/Watts) 6K / 5.4K 10K / 9K
INPUT
Nominal Voltage 220/230/240Vac(L+N+PE)
Operating Voltage
Range
120Vac-276Vac
Operating Frequency
Range
50Hz:45~55Hz,60Hz:54~66Hz
Power Factor ≥0.99
Bypass Voltage Range Max.voltage:  220V:+25%(Optional +10%,+15%,+20% )
          230V:+20%(Optional +10%,+15%)
240V:+15%(Optional +10% )
                                   Min. voltage: -45% (Optional -20%,-30%)
ECO Range Same as bypass
Harmonic Distortion
(THDi)
≤5%(100% non-linear load)
OUTPUT
Output Voltage 220/230/240Vac
Power Factor 0.9
Voltage Regulation ±1%
Frequency Line Mode ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional)
Bat. Mode (50/60±0.1)Hz
Crest Factor 3:1
Harmonic Distortion
(THDv)
≤2% with linear load
≤5% with non-linear load
Waveform Pure Sinewave
Transfer Time Utility to Battery : 0ms; Utility to Bypass: 0ms
EFFICIENCY
Efficiency Up to 94%
BATTERY
Battery Voltage Optional Voltage: ±96/108/120Vdc
Typical Recharge Time 6-8 hours (To 90% capacity)
Charging Current Maximum current 10A;
PROTECTION
Overload Line Mode Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode
Bypass Mode 40A(Input breaker) 60A(Input breaker)
Short Circuit Hold Whole System
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Battery Low Alarm and Switch off
INDICATORS
Audible & Visual
alarms
Line Failure, Battery Low, Overload, System Fault
Status LED & LCD
Display
Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading On The LCD
Display
Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner
Temperature & Remaining Battery  Backup Time
MANAGEMENT
Communication
Interface
RS232,USB, Parallel Port, SNMPcard(Optional), Relay card (Optional)
ENVIRONMENT
Operating
Temperature
0℃~40℃
Storage Temperature -25℃~55℃
Humidity Range 0~95% (Non-condensing)
Altitude < 1500m
Noise Level <55dB
PHYSICAL
Dimension
W×D×H (mm)
443×580×131 (3U)
Net Weight (kg) 19 20
STANDARDS
Noise Suppression Complies with EN62040-2
Safety IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
BATTERY PACK
Model EXBR±120V
Battery type&
Max.quantity
7Ah×20/9Ah×20
Dimensions
W×D×H (mm)
443×720×131 (3U)
Net Weight (kg) 65/75